6-45
IM WX104-01E
1
2
3
4
5
6
7
8
9
Index
Conf
gur
ng the DX1000/DX2000
Report
Click to display the channel selection screen.
Channel selection screen
Click the channel you wish to set up
Report knd
Select the type of report to be created.
Settngs
Descrpton
OFF
Do not create a report.
Hour
Creates hourly reports.
Day
Creates daily reports.
Hour+Day
Creates hourly and daily reports.
Day+Week
Creates daily and weekly reports.
Day+Month
Creates daily and monthly reports.
Day, Week day, and Tme (hour)
Set the date or day of the week and the time when the report is to be created. The
specified date/time is when the report file is divided. Set the values in the range
indicated below. Items with a dash are invalid.
Report Type
Day
Week day
Tme
Hour
-
-
0 to 23
Day
1 to 28*
-
0 to 23
Hour+Day
-
-
0 to 23
Day+Week
-
SUN to SAT
0 to 23
Day+Month
1 to 28*
-
0 to 23
* You cannot specify 29, 30, or 31.
Report Channel No.
The report is output in order by this number.
Use
Select [ON] for the report channels to be used.
CH No.
Set the channel to assign to the report channel. All channels can be assigned, but
reports are not created for channels set to [Skip] or [OFF] even if they are assigned.
In the stacked bar graph display, report data is displayed in the following groups.
However, only channels that have the same unit as the first group in the channel are
displayed.
No.
1
2
3
4
5
6
Report Groups (DX1000)
R01 to R06
R07 to R12
R13 to R18
R19 to R24
—
—
Report Groups (DX2000)
R01 to R10
R11 to R20
R21 to R30
R31 to R40
R41 to R50
R51 to R60
Sum Scale
Set the sum scale to [/s] to [/day] to match the unit of the measured value.
Example: If the unit of the measured value is “m
3
/min,” select [/min].
OFF Sums as-is the measured data per scan interval.