Index – Yokogawa DAQWORX User Manual
Page 182

6-55
IM WX104-01E
1
2
3
4
5
6
7
8
9
Index
Conf
gur
ng the DX1000/DX2000
Command settng
• Clent command No.
Select from 1 to 16 for the transmitted command numbers to be configured.
• Command
Set the command type.
Settngs
Descrpton
Read
Read to the external input channel (16-bit signed integer type) from the server.
R-Math
Read to the communication input data (32-bit floating point type) from the
server.
Write
Write the measurement channel (16-bit signed integer type) to the server.
W-Math
Write the measurement channel (32-bit signed integer type) to the server.
Exchange-M Read to the communication input data (32-bit floating point type) from the
server/write the custom display value to the server (release numbers 4 and
later).
[Read] can be selected on DX2000s with the external input channel (/MC1 option) installed.
[R-Math], [W-Mat], and [Exchange-M ] can be selected on models with the computation
function (/M1 or /PM1 option) installed.
• Start channel/End channel (clent channels)
Enter the first and last channel numbers of input/output. The range of channels that
you can enter varies depending on the command type as follows:
Read: 201 to 440, R-Math: C01 to C60, Write: 1 to 48, W-Math: 101 to 160
Exchange-M (release numbers 4 and later): C01 to C60
• Connected to (server number)
Select the server number from 1 to 16.
• Regster
Set the register number of the server.
For an input register, select in the range of 30001 to 39999 and 300001 to 365536.
For a hold register, select in the range of 40001 to 49999 and 400001 to 465536.
The register numbers you can specify vary depending on the command type. See
section 6/3 of the DX1000/DX1000N/DX2000 Communication Interface User’s Manual
(IM04L41B01-17E).
• Type
Select INT16, UINT16, INT32_B, INT32_L, UINT32_B, UINT32_L, FLOAT_B, or
FLOAT_L.
The register numbers you can specify vary depending on the command type. See
section 6.3 of the DX1000/DX1000N/DX2000 Communication Interface User’s Manual
(IM04L41B01-17E).
In release number 3, FLOAT has been added as a data type for measurement channel
data and computation channel data.
6.5 Enterng Basc Settngs