• Wait action
Set the wait action type to [Shift] or [Within]. To disable the wait action, select [Off].
• Wait zone number
Select the wait zone number from [1] to [5]. This item is available only when [Wait
action] is set to [Shift] or [Within].
PV Event
Set the PV Event.
Click this tab
• Loop
Set the target loop number [1] to [6] of the PV event (only selectable loop numbers).
Up to 16 events can be assigned. Select [Off] (initial setting) for the number of the
loops to which the event is not to be assigned.
• Type
Select the type of PV event from the following.
PV high-limit, PV low-limit, deviation high-limit, deviation low-limit, deviation high & low
limit, deviation within high & low limits, SP high-limit, SP low-limit , output high-limit ,
and output low-limit
• Value
Set the value in the following range according to the type of PV event.
PV/SP event: EU (0.0 to 100.0%) of the measurement span
Deviation high-limit event/low-limit event: EUS (–100.0 to 100.0%) of the measurement
span
Deviation high & low limit/within high & low limits: EUS (0.0 to 100.0%) of the
measurement span
Output event: –5.0% to 105.0% of output (% indication only for output events)
PV event display
A bar showing that the PV event was set is displayed in the upper part of the program
pattern screen display screen.