5 control conditions at power-up – Rockwell Automation 8520 9/Series CNC Lathe User Manual
Page 43
Basic Control Operation
Chapter 2
2-21
After powering up the control or performing a control reset operation (see
page 2-4), the control assumes a number of initial operating conditions.
These are listed below:
Initial Password Access is assigned to the level that was active when
power was turned off (provided that level is a power-up level selected in
access control). If the active level when power is turned off is not a
power-up level, then the control defaults to the next lower level that is a
power-up level. See page 2-23 on access control.
The control is placed in E-Stop. The control is not allowed to come out
of E-Stop if the default AMP is loaded at power-up, or if there is no
PAL program loaded in the system. An appropriate error message is
displayed.
The control defaults to one G-code from each of these groups (as set in
AMP):
Modal Group:
G-code
1
G00
Rapid traverse
G01
Linear interpolation
2
G17
Plane Selected
G18
Plane Selected
G19
Plane Selected
3
G90
Absolute
G91
Incremental
4
G22
Programmable Zone 2 and 3 (On)
G22.1
Programmable Zone 2 (Off) 3 (On)
G23
Programmable Zone 2 and 3 (Off)
G23.1
Programmable Zone 2 (On) 3 (Off)
5
G94
Feed per minute
G95
Feed per revolution
6*
G70
Inch mode
G71
Metric mode
18
G07
Radius Programming Mode
G08
Diameter Programming Mode
* This G code group is only established at power up. A control reset
will not change the last programmed state of this modal G code group.
To show the current operating conditions at any time, access the G-code
status screen as described in chapter 10. If you do this immediately after
power-up, it shows the initial operating conditions selected in AMP along
with other control power-up default conditions.
2.5
Control Conditions at
Power-Up