Chapter 4
Data File Organization and Addressing

4–5

Assign I/O addresses to fixed I/O controllers as shown in the table below:

Format

Explanation

O

Output

I

Input

:

Element delimiter

Slot number
(decimal)

fixed I/O controller: 0

O:e.s/b

e

left slot of expansion rack: 1
right slot of expansion rack: 2

I:e.s/b

.

Word delimiter. Required only if a word number is necessary as noted
below.

s

Word
number

Required if the number of inputs or outputs exceeds 16 for
the slot. Range: 0 – 255 (range accommodates
multi-word “specialty cards”)

/

Bit delimiter

b

Terminal
number

Inputs: 0 to 15
Outputs: 0 to 15

Examples (applicable to the controller shown on page 4-4):

O:0/4

Controller output 4 (slot 0)

O:2/7

Output 7, slot 2 of the expansion rack

I:1/4

Input 4, slot 1 of the expansion rack

I:0/15

Controller input 15 (slot 0)

I:0.1/7

Controller input 23 (bit 07, word 1 of slot 0)

Word addresses:

O:1

Output word 0, slot 1

I:0

Input word 0, slot 0

I:0.1

Input word 1, slot 0

Default Values: Your programming device will display an address more formally. For example,
when you assign the address I:1/4, the HHT shows it as I1:1.0/4 (Input file, file #, slot 1, word 0,
terminal 4).