Chapter 21
Move and Logical Instructions

21–3

Using Arithmetic Status Bits

C always reset

V always reset

Z set if the result is zero; otherwise reset

S set if the result is negative (most significant bit is set); otherwise reset

Application note: If you wish to move 1 word of data without affecting the
math flags, use a copy (COP) instruction with a length of 1 word instead of
using the MOV instruction. The COP instruction is discussed in chapter 22.

Masked Move

MVM

Output Instruction

(MVM)

MVM

MASKED MOVE
Source

B3:6

1111010011110101

Mask

00E0

Dest

B3:7

0000000011100000

F1

F2

F3

F4

F5

ZOOM on MVM –(MVM)– 2.3.0.0.2
NAME: MASKED MOVE
SOURCE: B3:6 1111 0100 1111 0101
MASK: 00E0 00E0
DEST: B3:7 0000 0000 1110 0000

EDT_DAT

HHT Ladder Display:

HHT Zoom Display:

Ladder Diagrams and APS Displays:

(online monitor mode)

The masked move instruction is a word instruction that moves a copy of the
data from a source location to a destination, and allows portions of the
destination data to be masked by a separate word.