Chapter 27
The Status File

27–19

Fault Classification

Processor

Description

User

Address

Error
Code
(Hex)

Runtime Errors

Non-User

Non-Recov

Recov

5/02

5/01,

Fixed

S:6

0020

A minor error bit is set at the end of the scan. (See S:5 minor
error bits.)

X

0021

Remote power failure of an expansion I/O rack occurred.

Note: A modular system that encounters an overvoltage or
overcurrent condition in any of its power supplies can
produce any of the I/O error codes listed on pages 27–21 and
27–22 (instead of code 0021). The overvoltage or
overcurrent condition is indicated by the power supply LED
being off.

ATTENTION: Fixed and FRN 1 to 4 SLC 5/01
processors – If the remote power failure occurred while
the processor was in the Run mode, error 0021 will
cause the major error halted bit (S:1/13) to be cleared
at the next powerup of the local rack.
SLC 5/02 processors and FRN 5 SLC 5/01 processors
– Power to the local rack does not need to be cycled to
resume the Run mode. Once the remote rack is
re-powered, the CPU will restart the system.

!

X

0022

User watchdog scan time exceeded.

X

0023

Invalid or non-existent STI interrupt file.

X

0024

Invalid STI interrupt interval (greater than 2550 ms or
negative).

X

0025

Excessive stack depth/JSR calls for STI routine.

X

0026

Excessive stack depth/JSR calls for I/O interrupt routine.

X

0027

Excessive stack depth/JSR calls for user fault routine.

X

0028

Invalid or non-existent “startup protection” fault routine file
value.

X

0029

Indexed address reference outside of entire data file space
(range of B3:0 through the last file).

X

002A

Indexed address reference beyond specific referenced data
file.

X