Chapter 27
The Status File

27–22

Fault Classification

Processor

Description

User

Address

Error
Code
(Hex)

I/O Errors

Non-User

Non-Recov

Recov

5/02

5/01,

Fixed

S:6

xx5C

M0–M1 file configuration error – user program M0–M1 file
size exceeds capacity of the module.

X

xx5D

Interrupt service requested is not supported by the processor.

X

xx5E

Processor I/O driver (software) error.

X

xx60 thru

xx6F

Identifies an I/O module specific recoverable major error.
Refer to the user manual supplied with the specialty module.

X

xx70 thru

xx7F

Identifies an I/O module specific non-recoverable major error.
Refer to the user manual supplied with the specialty module.

X

xx90

Interrupt problem on disabled slot.

X

xx91

A disabled slot has faulted.

X

xx92

Invalid or non-existent module interrupt subroutine file.

X

xx93

Unsupported I/O module specific major error.

X

xx94

In the run or test mode, a module has been detected as
being inserted under power. Can also mean that an I/O
module has reset itself.

X