Attach, Upload/download a program, Change processor operating modes – Rockwell Automation 1747-PT1, D1747NP002 Hand-Held Terminal User Manual
Page 171: Enter or remove a password/master password, Monitor program execution, Monitor and change data file values, Force i/o, Press the, Press, Attach . the following menu is displayed

Chapter 9
Configuring Online Communication
9–7
Attach
The Attach function initiates communication between the HHT and a
processor. The Attach function allows you to:
•
upload/download a program
•
change processor operating modes
•
clear the processor memory
•
enter or remove a password/master password
•
transfer memory between processor RAM and EEPROM
•
monitor program execution
•
monitor and change data file values
•
force I/O
•
search the user program for specific instructions and/or addresses
The function keys and menus vary depending on how the HHT and processor
programs relate. In this example, attach the HHT to node 4. Assume that the
HHT and processor programs are identical.
1. Start at the Who display:
Node Addr.
Device Max Addr./Owner
2
5/02
(31)
3
500–20
(31)
*** 4
5/01
(31)
0
APS
(31)
Node Addr: 2 Baud Rate: 19200
F1
F2
F3
F4
F5
DIAGNSTC
ATTACH
OFL
OWNER
NODE_CFG
Current Node
2. Press the
[
↓
]
, twice to select node 4.
The display appears as follows:
Node Addr.
Device Max Addr./Owner
*** 4
5/01
(31)
0
APS
(31)
1
TERMINAL
(31)
2
5/02
(31)
Node Addr: 4 Baud Rate: 19200
F1
F2
F3
F4
F5
DIAGNSTC
ATTACH
OFL
OWNER
NODE_CFG
Current Node
3. Press
[F3]
, ATTACH. The following menu is displayed:
File Name: 222
Prog Name:1000
File Name
Type
Size(Instr)
0
System
77
1
Reserved
0
2
222
Ladder
13
3
Ladder
1
F1
F2
F3
F4
F5
OFFLINE
UPLOAD
DWNLOAD
RUN
CLR_PRC
MODE
Display toggles between the
processor node address and
the processor operating
mode.
>