Chapter 6
Creating a Program

6–2

2. Press

[F3]

, PROGMAINT. Then press

[ENTER]

to view the additional

menu functions (as indicated by the > symbol in the lower right corner).
The following display appears:

File Name:

Prog Name:2345

File Name

Type

Size(Instr)

0

System

*

1

Reserved

*

2

Ladder

*

F1

F2

F3

F4

F5

EDT_DAT SEL_PRO EDT_I/O

OFL

CLR_MEM

>

3. Press

[F4]

, CLR_MEM. The following display appears:

File Name:

Prog Name:2345

File Name

Type

Size(Instr)

0

System

76

1

Reserved

0

2

Ladder

5

ARE YOU SURE?

F1

F2

F3

F4

F5

YES

OFL

NO

4. Press

[F2]

, YES. This clears the HHT memory and the following display

appears:

File Name:

Prog Name:DEFAULT

File Name

Type

Size(Instr)

0

System

*

1

Reserved

*

2

Ladder

*

F1

F2

F3

F4

F5

EDT_DAT SEL_PRO EDT_I/O

OFL

CLR_MEM

>

Configuring the Controller

After clearing the HHT memory, you must configure the processor and I/O
structure for your application.

Configuring the Processor

1. Press

[F2]

, SEL_PRO. Then press

[F1]

, TYPE. The following display

appears:

Type = 1747–L511

CPU–1K USER MEMORY

Series =
Memory Size = 1 K INSTRUCTIONS

F1

F2

F3

F4

F5

Type = 1747–L511

CPU–1K USER MEMORY

OTHER