18–9
MSG Instruction Error Codes
When an error condition occurs, the error bit ER is set. The lower byte of
the first word in the control block indicates the type of error:
Error Code
(decimal)
Error Code
(binary)
Error Code
(hex)
Description of Error Condition
2
0000 0010
02H
Target node is busy. The MSG instruction will automatically
reload. If other messages are waiting, the message is placed at
the bottom of the stack.
3
0000 0011
03H
Target node cannot respond because message is too large.
4
0000 0100
04H
Target node cannot respond because it does not understand the
command parameters.
5
0000 0101
05H
Local processor is offline.
6
0000 0110
06H
Target node cannot respond because requested function is not
available.
7
0000 0111
07H
Target node does not respond.
16
0001 0000
10H
Target node cannot respond because of incorrect command
parameters or unsupported command.
55
0011 0111
37H
Message timed out in local processor.
80
0101 0000
50H
Target node is out of memory.
96
0110 0000
60H
Target node cannot respond because file is protected.
241
1111 0001
F1H
Local processor detects illegal target file type.
231
1110 0111
E7H
Target node cannot respond because length requested is too
large.
235
1110 1011
EBH
Target node cannot respond because target node denies access.
236
1110 1100
ECH
Target node cannot respond because requested function is
currently unavailable.
250
1111 1010
FAH
Target node cannot respond because another node is file owner
(has sole file access).
251
1111 1011
FBH
Target node cannot respond because another node is program
owner (has sole access to all files).