Chapter 27
The Status File

27–18

Fault Classification

Processor

Description

User

Address

Error
Code
(Hex)

Powerup Errors

Non-User

Non-Recov

Recov

5/02

5/01,

Fixed

S:6

0001

NVRAM error.

X

0002

Unexpected hardware watchdog timeout.

X

0003

Memory module memory error.

X

0004

Memory integrity check failed (runtime).

X

Fault Classification

Processor

Description

User

Address

Error
Code
(Hex)

Going to Run Errors

Non-User

Non-Recov

Recov

5/02

5/01,

Fixed

S:6

0010

Processor does not meet proper revision level.

X

0011

The executable file number 2 is absent.

X

0012

The ladder program has a memory error.

X

0013

The required memory module is absent or either S:1/10 or
S:1/11 is not set (and the program requires it).

X

0014

Internal file error.

X

0015

Configuration file error.

X

0016

Startup protection after power loss. Error condition exists at
powerup when bit S:1/9 is set and powerdown occurred while
running.

X