Interrupts – 5/02 Processor Only

Chapter 30
Understanding Selectable Timed

30–7

STD/STE Zone Example

In the program below, the STI function is in effect. The STD and STE
instructions in rungs 6 and 12 are included in the ladder program to avoid
having STI subroutine execution at any point in rungs 7 thru 11.

The STD instruction (rung 6) resets the STI enable bit and the STE
instruction (rung 12) sets the enable bit again. The STI timer increments and
may time out in the STD zone, setting the pending bit S:2/0 and overrun bit
S:5/10.

The first pass bit S:1/15 and the STE instruction in rung 0 are included to
insure that the STI function is initialized following a power cycle. You
should include this rung any time your program contains an STD/STE zone
or an STD instruction.

] [

S:1

15

( )

STI interrupt

execution will

not occur

between STD

and STE.

END

0

STD

SELECTABLE TIMED DISABLE

STE

SELECTABLE TIMED ENABLE

] [

] [

( )

] [

] [

( )

] [

] [

STE

SELECTABLE TIMED ENABLE

( )

] [

] [

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

Program File 2