5/02 Processor Only

Chapter 29
Understanding the User Fault Routine –

29–2

Recoverable User Faults

GOING TO RUN ERRORS

0013

The required memory module is absent or either S:1/10 or S:1/11 is not set
(and the program requires it).

0016

Startup protection after power loss. Error condition exists at powerup when
bit S:1/9 is set and powerdown occurred while running.

RUNTIME ERRORS

0020

A minor error bit is set at the end of the scan.

0029

Indexed address reference outside of entire data file space (range of B3:0
through the last file).

INSTRUCTION ERRORS

0032

Sequencer length/position points past end of data file.

0033

Length of LFU, LFL, FFU, FFL, BSL, or BSR points past end of data file.

0034

A negative value for a timer accumulator or preset value was detected.

0036

Invalid value for a PID parameter. Code 0036 is discussed further in
chapter 26.