Monitoring Controller Operations

12–10

To change online data, begin by monitoring the program online while the
processor is in either the Run or Test Continuous Scan (CSN) mode.

] [

] [

] [

2.0.0.0.1

F1

F2

F3

F4

F5

( )

( )

] [

] [

] [

MODE

FORCE

EDT_DAT

SEARCH

RUN

] [

] [

( )

XIC:I1:1.0/0 NO FORCE

(RES)

(CTU)

Observe the following:

XIC instruction C5:0/15 (count–up bit) and rung 1 are true whenever rung
0 is true, and false whenever rung 0 is false.

Each time rung 0 makes a false to true transition, the accumulator value
increments. Position the cursor on the CTU instruction and press [

ZOOM

]

to display the counter accumulator value.

When the accumulator value equals the preset, 3, XIC instruction C5:0/13
(done bit) goes true, making rung 2 true. The instruction remains true as
long as the accumulator is greater than or equal to the preset value.

To change the counter preset or accumulator values or the status bits:

1. Press EDT_DAT from either the zoom display or the online monitor

display. A screen similar to the one below appears.

Counter

C5:0
CU

CD

DN

OV

UN

UA

STATUS

0

0

1

0

0

0

PRESET

3

ACCUM

16

STATUS=001000

RUN

F1

F2

F3

F4

F5

NEXT_PG PREV_PG

ADDRESS NEXT_FL PREV_FL

In this display, the accumulator (ACCUM) is 16 and the done bit DN (bit
13) is set. Reset the counter by making rung 4 true momentarily. The
accumulator value and the done bit are reset to zero.

2. Change the preset and accumulator values from the EDT_DAT screen.

Press the down arrow key to place the cursor on the preset. Type

32767

(maximum value) and press [

ENTER

]. Press the down arrow key to place

the cursor on the accumulator (ACCUM). Type

32767

(maximum value)

and press [

ENTER

]. The display appears as follows:

Counter

C5:0
CU

CD

DN

OV

UN

UA

STATUS

0

0

1

0

0

0

PRESET

32767

ACCUM

32766

STATUS=32766

RUN

F1

F2

F3

F4

F5

NEXT_PG PREV_PG

ADDRESS NEXT_FL PREV_FL