beautypg.com

Status file fault display – Rockwell Automation 1747-PT1, D1747NP002 Hand-Held Terminal User Manual

Page 404

background image

Chapter 28
Troubleshooting Faults

28–2

The status file displays applying to major and minor faults are shown below.
The displays are accessible offline and online under the EDT DAT function.
Press NEXT__FL until you get to the status file. Move between displays by
pressing NEXT__PG or PREV__PG.

D

C

B

A

F1

F2

F3

F4

F5

Status File
S2:5 Minor Fault 0000 0000 0000 0000
S2:6 Fault Code 0000H
Desc: No Error
S2:29 Err File: 0 Indx Cross File: No
S2:24 Index Reg: 0 Single Step: No
S2:5/0 = 0 PRG
ADDRESS NEXT FL PREV FL NEXT PG PREV PG

F1

F2

F3

F4

F5

Status File
Arithmetic Flags S:0 Z:0 V:0 C:0
S2:0 Proc Status 0000 0000 0000 0000
S2:1 Proc Status 0000 0000 1000 0001
S2:2 Proc Status 1000 0000 0000 0010

S2:0/0 = 0 PRG
ADDRESS NEXT FL PREV FL NEXT PG PREV PG

F1

F2

F3

F4

F5

Status File
S2:5 Minor Fault 0000 0000 0000 0000
S2:6 Fault Code 0000H
Desc: No Error
S2:3L Program Scan [x10mS] last: 0
S2:3H Watchdog [x10mS] 10
S2:5/0 = 0 PRG
ADDRESS NEXT FL PREV FL NEXT PG PREV PG

F1

F2

F3

F4

F5

Status File
Arithmetic Flags S:0 Z:0 V:0 C:0
S2:0 Proc Status 0000 0000 0000 0000
S2:1 Proc Status 0000 0000 1000 0001
S2:2 Proc Status 1000 0000 0000 0010

S2:0/0 = 0 PRG
ADDRESS NEXT FL PREV FL NEXT PG PREV PG

SLC 5/02 Processors

Fixed and SLC 5/01 Processors

D

C

B

A

A, B, C, and D in the figure above indicate the location of fault information:

A –Word S2:1. Bit S2:1/13 in this word is the major fault bit. Clear the fault
bit at this display by setting S2:1/13 to 0. Press the

[F1]

, ADDRESS, type

S:1/13

, press

[ENTER]

, type 0, press

[ENTER]

.

B –Word S2:5. Minor fault bits. Clear the fault at this display by setting the
bits to 0. Press the

[F1]

, ADDRESS, type in the address of the minor fault

bit, press

[ENTER]

, type

0

, press

[ENTER]

.

C –Word S2:6. Fault code. Clear the code at this display by setting S2:6 to
0. Press the

[F1]

, ADDRESS, type in the address of the fault code, press

[ENTER]

, type

0

, press

[ENTER]

.

D – Fault description. A textual description of the fault code. Clear at this
display by setting word S2:6 to 0.

The following tables list error types as:

Powerup

Going-to-Run

Runtime

User Program Instruction

I/O

Each table lists the error code description, the probable cause, and the
recommended corrective action.

Status File Fault Display

Error Code Description,
Cause, and
Recommended Action