Chapter 16
Bit Instructions

16–5

(L)

Output Latch, Output Unlatch

OTL, OTU

Output Instruction

(U)

(L)

B3

6

(U)

B3

6

F1

F2

F3

F4

F5

ZOOM on OTL –(L)– 2.3.0.0.2
NAME: OUTPUT LATCH
BIT ADDR: B3/6 *********0******

EDT_DAT

HHT Ladder Display:

HHT Zoom Display:

Ladder Diagrams and APS Displays:

F1

F2

F3

F4

F5

ZOOM on OTU –(U)– 2.4.0.0.2
NAME: OUTPUT UNLATCH
BIT ADDR: B3/6 *********0******

EDT_DAT

(online monitor mode)

Logic States:

Rung

New

1
1
1
0
0
1
0
0

True

False

True

False

True

False

True

False

1

0

1

0

State

Condition

Previous

State

Instruction

OTL

OTU

These are retentive output instructions that can be used in a pair for the data
table bit they control. Possible logic states are indicated in the table above.
OTL and OTU instructions can also be used to initialize data values at the bit
level.

When you assign an address to the OTL instruction that corresponds to the
address of an external output terminal, the output device wired to this
terminal is energized when the bit in memory is set (1). An OTU instruction
with the same address as the OTL instruction resets (0) the bit in memory.

Output Latch (OTL), Output
Unlatch (OTU)