beautypg.com

Rockwell Automation 1747-PT1, D1747NP002 Hand-Held Terminal User Manual

Page 415

background image

5/02 Processor Only

Chapter 29
Understanding the User Fault Routine

29–3

I/O ERRORS

Recoverable only if you disable slot xx in the

user fault routine

xx50

A rack data error is detected.

xx52

A module required for the user program is detected as missing or removed.

xx53

At going-to-run, a user program declares a slot as unused, and that slot is
detected as having an I/O module inserted. Can also mean that the I/O
module has reset itself.

xx54

A module required for the user program is detected as being the wrong
type.

xx55

A module required for the user program is detected as having the wrong
I/O count or wrong I/O driver.

xx57

A specialty I/O module has not responded to a lock shared memory
command within the required time limit.

xx59

A specialty I/O module has not responded to a command as being
completed within the required time limit.

xx5A

Hardware interrupt problem.

xx5B

G file configuration error – User program G file size exceeds capacity of the
module.

xx5C

M0–M1 file configuration error – User program M0–M1 file size exceeds
capacity of the module.

xx5D

Interrupt service requested is not supported by the processor.

xx5E

Processor I/O driver (software) error.

xx60

thru

xx6F

Identifies an I/O module specific recoverable major error. Refer to the user
manual supplied with the module.