Sequencer load (sql), Slc 5/02 processors only, Entering parameters – Rockwell Automation 1747-PT1, D1747NP002 Hand-Held Terminal User Manual

Page 329

background image

Chapter 24
Sequencer Instructions

24–7

SLC 5/02 Processors Only

Sequencer Load

SQL

Output Instruction

(SQL)

(EN)

(DN)

SQL

SEQUENCER LOAD
File

#N7:30

Source

I:1.0

Control

R6:4

Length

4

Position

0

HHT Ladder Display:

HHT Zoom Display:

Ladder Diagrams and APS Displays:

(online monitor mode)

ZOOM on SQL –(SQL)– 2.3.0.0.2
NAME: SEQUENCER LOAD
FILE: #N7:30 LENGTH: 4
SOURCE: I1:1.0 POSITION:0
CONTROL: R6:4
EN EU DN EM
0 0 0 0
EDT_DAT

F1

F2

F3

F4

F5

This instruction loads data into a sequencer load file. The source of this data
can be an I/O or storage word address, a file address, or a program constant.

Entering Parameters

File – This is the address of the sequencer file where the source data is
loaded into. You must use the file indicator # for this address.

Source – This can be a word address, file address, or a program constant
(–32768 to 32767) indicating the value or location whose contents are
loaded into the sequencer file. For input addresses, the HHT requires that
you enter the slot and word number. For example, I:3.0.
If the source is a file address, its file length will be equal to the length of
the sequencer load file (LENGTH). The two files will track
automatically, per the position value.

Control – This is a control file address. The status bits, length value, and
position value are stored in this element. Do not use the control file
address for any other instruction.
The 3-word control element:

EN DN ER

15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00

Length

Position

Sequencer Load (SQL)