Chapter 26
PID Instruction

26–20

Notes on Operation

A 3-digit BCD thumbwheel is wired to an input
module at I1:1.0 (range 0–100).

A pushbutton wired to I1:2.0/0 accepts the
thumbwheel value.

A selector switch for auto/manual mode is wired
to I1:2.0/1 (auto) and I1:2.0/2 (manual).

N7:0 stores the value entered on the
thumbwheel switch.

N7:2 stores an intermediate calculation.

N7:8 is the PID control variable address.

N7:10 is the control block address of the PID
instruction.

N7:26 Percent output is updated automatically
by the PID instruction.

] [

N7:10

1

[OSR]

B3

0

( )

B3

3

MUL

MULTIPLY
Source A

N7:0

Source B

16384

Dest

N7:2

LIM

LIMIT TEST
Low Lim

0

Test

N7:0

High Lim

100

FRD

FROM BCD
Source

I1:1.0

Dest

N7:0

DDV

DOUBLE DIVIDE
Source

100

Dest

N7:8

] [

I:2.0

0

(U)

S:5

0

] [

I:2.0

1

Accept CV

Error – Out of Range

Auto

] [

I:2.0

2

Manual

(L)

N7:10

1

(U)

N7:10

1

A/M Bit

A/M Bit

A/M Bit

LIM

LIMIT TEST
Low Lim

101

Test

N7:0

High Lim

–1

Example – To Manually Control the CV Output