Chapter 20
Math Instructions

20–15

Convert from BCD

FRD

Output Instruction

(FRD)

Fixed, SLC 5/01 Processors

FRD

FROM BCD
Source

N7:0
2620

Dest

N7:1
2620

FRD

FROM BCD
Source

S:13

00000557

Dest

N7:1

557

F1

F2

F3

F4

F5

ZOOM on FRD –(FRD)– 2.3.0.0.2
NAME: FROM BCD
DEST: N7:1 557
SOURCE: S:13 1367 (decimal)

EDT_DAT

HHT Ladder Display:

HHT Zoom Display:

Ladder Diagrams and APS Displays:

F1

F2

F3

F4

F5

ZOOM on FRD –(FRD)– 2.3.0.0.2
NAME: FROM BCD
SOURCE: N7:0 9760 (decimal)
DEST: N7:1 2620

EDT_DAT

(online monitor mode)

BCD

BCD

Fixed, SLC 5/01 Processors

SLC 5/02 Processors

SLC 5/02 Processors

Use this instruction when you want to convert BCD values to integer or
decimal values.

Entering Parameters

Source – word address of the value in BCD to be converted to
integer/decimal. With SLC 5/02 processors, the source parameter can be
a word address in any data file, or it can be the math register, S:13. With
fixed and SLC 5/01 processors, the source can only be the math register.
If the math register is the source, 32,767 is the maximum value. If a word
address is used, 9999 is the maximum value.

Destination – word address to contain the converted decimal/integer
value.

Convert from BCD (FRD)