Interrupts – 5/02 Processor Only

Chapter 30
Understanding Selectable Timed

30–8

The STS instruction can be used to condition the start of the STI timer upon
entering the Run mode – rather than starting automatically. It can also be
used to set up or change the file number or setpoint/frequency of the STI
routine that will be executed when the STI timer expires.

This instruction is not required to configure a basic STI interrupt application.

Selectable Timed Start

STS

Output Instruction

STS

SELECTABLE TIMED START
File

3

Time (x10 ms)

30

(STS)

HHT Ladder Display:

HHT Zoom Display:

Ladder Diagrams and APS Displays:

(monitor mode)

F1

F2

F3

F4

F5

ZOOM on STS –(STS)– 2.9.0.0.1
NAME: SELECTABLE TIMED START
FILE: 3 3
TIME: 30 30

EDT_DAT

STS Selectable Timed Start Immediately – The STS instruction requires
you to enter two parameters, the STI file number and the STI setpoint. Upon
a true execution of the rung, this instruction will enter the file number and
setpoint/frequency in the status file (S:31, S:30), overwriting the existing
data. At the same time, the STI timer is reset and begins timing; at timeout,
the STI subroutine execution occurs. When the rung goes false, the STI
function remains enabled at the setpoint and file number you’ve entered in
the STS instruction.

STS Instruction