Chapter 8
Compiling and Saving a Program
8–3
If you selected SAVE_CT, you are returned to the editing display when
the compile and save is complete. If you selected SAVE_EX, the
following display appears:
File Name: 222
Prog Name:1000
File Name
Type
Size(Instr)
0
System
77
1
Reserved
0
2
222
Ladder
13
3
Ladder
1
F1
F2
F3
F4
F5
CHG_NAM CRT_FIl EDT_FIL
OFL
DEL_FIL
>
MEM_MAP
Available Compiler Options
[F1] Future Access (All Processors)
This option allows you to protect proprietary program data and algorithms.
Important: The protection takes effect only after the program is
downloaded to a controller. The protection does not allow
online access to the processor unless a matching copy of the
online processor program is resident on the terminal hard disk
or in the HHT. Otherwise you are not able to upload the
program.
Yes: Online access to the processor program and data table using a
programming terminal is unrestricted. This is the default.
No: Online access to the processor program and data table is not permitted
unless a matching copy of the online processor program is in the HHT. You
cannot:
•
monitor the program
•
enter or change the processor password
•
upload the online processor program to HHT RAM
•
transfer the program from the processor memory to a memory module
However, you can:
•
clear the processor memory
•
download a different program to the processor
•
change the processor mode
Important: If you lose or delete the offline copy of the program, you cannot
access the program in the controller. You must clear the
controller memory and re–enter the program.