Page 252

Instructions
Chapter 18
I/O Message and Communication
18–6
After you enter an address, the display changes to the following.
7. Enter Message Length –
F1
F2
F3
F4
F5
ZOOM on MSG –(MSG)– 2.0.0.0.*
NAME: MESSAGE READ/WRITE
MSG TYPE: WRITE LD/LS ADDR:N7:40
TARGET: 500 CPU TARG NODE: 5
CTRL BLK: N7:0 TARG OS/AD:N7:6
CTRL BLK 7 WORDS MSG LEN: 0
ENTER MESSAGE LENGTH:0
This is the length of the message in elements. The 1–word elements are
limited to a maximum length of 41. The 3–word elements (T,C,R) are
limited to a maximum length of 13.
The destination file type determines the number of words that are
transferred. Examples: A MSG read instruction specifying a target file
type C (counter), a destination file type N (integer), and a length value of
1 will transfer 1 word of information. A MSG read instruction specifying
a target file type N, a destination file type C, and a length value of 1 will
transfer 3 words.
The message length is the final parameter. After you enter it, the display
changes to the following.
F1
F2
F3
F4
F5
ZOOM on MSG –(MSG)– 2.0.0.0.*
NAME: MESSAGE READ/WRITE
MSG TYPE: WRITE LD/LS ADDR:N7:40
TARGET: 500 CPU TARG NODE: 5
CTRL BLK: N7:0 TARG OS/AD:N7:6
CTRL BLK 7 WORDS MSG LEN: 2
SELECT MESSAGE TYPE.
READ WRITE ACCEPT
Pressing
[F5]
, ACCEPT, completes the entry of parameters. If you must
change any of the parameters, you can run through the entry of
parameters again before you press ACCEPT.