C00801
C00802
C00803
C00804
C00805
Parameter | Name:
C00801 | L_MPot_1: Lower limit
Data type: INTEGER_16
Index: 23774
d
= 5CDE
h
FB: Lower limit of the motor potentiometer function
Setting range
(min. value | unit | max. value)
Lenze setting
-199.99
%
199.99 -100.00 %
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100
Parameter | Name:
C00802 | L_MPot_1: Acceleration time
Data type: UNSIGNED_16
Index: 23773
d
= 5CDD
h
FB: Acceleration time of the motor potentiometer function
Setting range
(min. value | unit | max. value)
Lenze setting
0.1
s
6000.0 10.0 s
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 10
Parameter | Name:
C00803 | L_MPot_1: Deceleration time
Data type: UNSIGNED_16
Index: 23772
d
= 5CDC
h
FB: Deceleration time of the motor potentiometer function
Setting range
(min. value | unit | max. value)
Lenze setting
0.1
s
6000.0 10.0 s
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 10
Parameter | Name:
C00804 | L_MPot_1: Inactive fct.
Data type: UNSIGNED_8
Index: 23771
d
= 5CDB
h
FB: Selection of the response if the motor potentiometer is deactivated via input bInAct
Selection list
(Lenze setting printed in bold)
Info
0 Retain value
Keep output value
1 Deceleration to 0
Deceleration via ramp to 0
2 Deceleration to lower limit
Deceleration via ramp to the lower limit (
)
3 Without ramp to 0
Step change to 0
4 Without ramp to lower limit
Jump to lower limit (
)
5 Acceleration to upper limit
Acceleration via ramp to upper limit (
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00805 | L_MPot_1: Init fct.
Data type: UNSIGNED_8
Index: 23770
d
= 5CDA
h
FB: Selection of the response at device switch-on
Selection list
(Lenze setting printed in bold)
0 Load last value
1 Load lower limit
2 Load 0
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1