17 function library – Lenze 8400 HighLine User Manual
Page 1347
Lenze · 8400 HighLine · Referenzhandbuch · DMS 10.0 EN · 06/2014 · TD05/TD14
1347
17
Function library
17.1
Function blocks
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Setting is bit coded:
Setting
• Lenze setting: 0x02
Bit 0 Setpoint angle without gearbox
factor
0 = Evaluation of the setpoint angle
with gearbox factor.
1 = Evaluation of the setpoint angle
without gearbox factor.
Bit 1 Angle correction with polynomial
0 = Angle correction without
downstream polynomial.
1 = Angle correction with
downstream polynomial.
Bit 2 External angle correction
0 = Internal angle correction
1 = External angle correction
•
From version 13.00.00
Bit 3 Reserved
...
Bit 7
0
16384 Divisor for actual value zero pulse
• Number of signals to be received
at least until synchronisation gets
active.
• Initialisation: 0 (≡ 1)
Note: The settings 0 and 1 are functionally
identical. If 0 or 1 is set, at least one pulse is
required in order that the synchronisation
gets active.
0
16384 Divisor for setpoint zero pulse
• Number of signals to be received
at least until synchronisation gets
active.
• Initialisation: 0 (≡ 1)
Note: The settings 0 and 1 are functionally
identical. If 0 or 1 is set, at least one pulse is
required in order that the synchronisation
gets active.
Parameter
Possible settings
Info