1 identifiers of the parameter data objects, 2 user data, Identifiers of the parameter data objects – Lenze 8400 HighLine User Manual
Page 724: User data, 11 system bus "can on board
![background image](/manuals/566310/724/background.png)
11
System bus "CAN on board"
11.9
Parameter data transfer
724
Lenze · 8400 HighLine · Referenzhandbuch · DMS 10.0 EN · 06/2014 · TD05/TD14
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
11.9.1
Identifiers of the parameter data objects
In the Lenze setting, the basic identifiers of the SDOs are preset according to the "Predefined
Connection Set".
The identifiers of the parameter data objects SDO1 and SDO2 result from the basic identifier and
the node address set under code
Identifier = basic identifier + node address
11.9.2
User data
Structure of the user data of the parameter data telegram
The following subchapters provide detailed information on user data.
Object
Direction
Lenze-Base-ID
CANopen-Base-ID
from device
to device
dec
hex
dec
hex
SDO1
(Parameter data channel 1)
TSDO1
1408
580
1408
580
RSDO1
1536
600
1536
600
SDO2
(Parameter data channel 2)
TSDO2
1472
5C0
1472
5C0
RSDO2
1600
640
1600
640
Heartbeat
1792
700
1792
700
Boot-up
1792
700
1792
700
1st byte
2nd byte 3rd byte
4th byte
5th byte
6th byte
7th byte
8th byte
Command
Index
Subindex
Data 1
Data 2
Data 3
Data 4
LOW byte
HIGH
byte
LOW word
HIGH word
LOW byte
HIGH byte
LOW byte
HIGH byte
Note!
For the user data, the Motorola format is used.
Parameter data telegram examples