Parameter | Name:
C00990 | Flying restart fct.: Activation
Data type: UNSIGNED_8
Index: 23585
d
= 5C21
h
Switch on/activate flying restart circuit for non-feedback drive systems
Selection list
(Lenze setting printed in bold)
0 Off
1 On
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00991 | Flying restart fct.: Process
Data type: UNSIGNED_16
Index: 23584
d
= 5C20
h
Selection of the starting value and the speed search range for the flying restart function
Selection list
(Lenze setting printed in bold)
Info
0 0...+n | Start: +10 Hz
Search positive speed range (0 ... +n) with a start
frequency of +10 Hz
1 -n...0 | Start: -10 Hz
Search negative speed range (-n ... 0) with a start
frequency of -10 Hz
2 -n...+n | Start: +10 Hz
Search negative and positive speed range (-n ... n) with a
start frequency of +10 Hz
3 -n...+n | Start: -10 Hz
Search negative and positive speed range (-n ... n) with a
start frequency of -10 Hz
4 -n...+n | Start: Cx992
Search the negative and positive speed range (-n ... n)
with the start frequency set in
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00992 | Flying restart fct.: Start frequency
Data type: INTEGER_16
Index: 23583
d
= 5C1F
h
Manual selection of the starting value for the flying restart function
• Only active if
= 4
Setting range
(min. value | unit | max. value)
Lenze setting
-200
Hz
200 10 Hz
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00993 | Flying restart fct: Int. time
Data type: UNSIGNED_16
Index: 23582
d
= 5C1E
h
Time constant of the angular difference controller of the flying restart function
• The time constant is to amount between 60 ... 300 ms.
Setting range
(min. value | unit | max. value)
Lenze setting
0.0
ms
6000.0 300.0 ms
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 10