C02200 | ls_writeparamlist: function, C02210 | ls_writeparamlist: motor control, C02200/1 – Lenze 8400 HighLine User Manual
Page 1097: C02200/2, Des from code, C02210, C02210/1, C02210/2, C02210/3, C02210/4
![background image](/manuals/566310/1097/background.png)
Lenze · 8400 HighLine · Referenzhandbuch · DMS 10.0 EN · 06/2014 · TD05/TD14
1097
15
Parameter reference
15.2
Parameter list | C02200
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C02200
C02210
C02212
Parameter | Name:
C02200 | LS_WriteParamList: Function
Data type: UNSIGNED_8
Index: 22375
d
= 5767
h
From version 12.00.00
Configuration of which parameter lists are to be subject to the "
" function.
Selection list
0 Off
1 On
Subcodes
Lenze setting
Info
C02200/1
1: On
Definable parameter list
C02200/2
0: Off
Motor data parameter list
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C02210 | LS_WriteParamList: Motor control
Data type: UNSIGNED_8
Index: 22365
d
= 575D
h
From version 12.00.00 onwards
: Parameter values (1st value ... 4th value) for optional
Selection list
2 SC: Servo control ASM
3 SLPSM: Sensorless PSM
4 SLVC: Vector control
6 VFCplus: V/f linear
7 VFCplus: V/f linear + encoder
8 VFCplus: V/f quadr
9 VFCplus: V/f quadr + encoder
10 VFCplus: V/f definable
11 VFCplusEco: V/f energy-saving
Subcodes
Lenze setting
Info
C02210/1
6: VFCplus: V/f linear
: c6_val1
C02210/2
6: VFCplus: V/f linear
: c6_val2
C02210/3
6: VFCplus: V/f linear
: c6_val3
C02210/4
6: VFCplus: V/f linear
: c6_val3
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C02212 | LS_WriteParamList: VFC: V/f base frequency
Data type: UNSIGNED_16
Index: 22363
d
= 575B
h
From version 12.00.00 onwards
: Parameter values (1st value ... 4th value) for optional
Setting range
(min. value | unit | max. value)
7.5
Hz
2600.0
Subcodes
Lenze setting
Info
C02212/1
50.0 Hz
: c15_val1
C02212/2
50.0 Hz
: c15_val2
C02212/3
50.0 Hz
: c15_val3
C02212/4
50.0 Hz
: c15_val4
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 10