Parameter reference
15.2
Parameter list | C00059
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00059
C00061
C00062
C00064
Parameter | Name:
C00059 | Appl.: Reference frequency C11
Data type: UNSIGNED_32
Index: 24516
d
= 5FC4
h
Display of the field frequency which corresponds to the reference speed set in
Display range
(min. value | unit | max. value)
0.00
Hz
1300.00
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100
Parameter | Name:
C00061 | Heatsink temperature
Data type: INTEGER_16
Index: 24514
d
= 5FC2
h
Display of the current heatsink temperature
Display range
(min. value | unit | max. value)
-50
°C
150
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00062 | Temperature inside the controller
Data type: INTEGER_16
Index: 24513
d
= 5FC1
h
From version 11.00.00
Display of the current temperature inside the controller
Display range
(min. value | unit | max. value)
-200
°C
200
Subcodes
Info
C00062/1
Interior temperature of CU
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00064 | Device utilisation (Ixt)
Data type: INTEGER_16
Index: 24511
d
= 5FBF
h
Display of the device utilisation Ixt in different time resolutions
• If the value displayed here exceeds the threshold set in
, the fault message "OC5: Device overload (Ixt)"
is output and the fault response set in
is executed (default setting: "Warning").
Display range
(min. value | unit | max. value)
0.00
%
250.00
Subcodes
Info
C00064/1
Device utilisation (Ixt)
• Maximum value of the pulse utilisation (C00064/2)
and permanent utilisation (C00064/3).
C00064/2
Device utilisation (Ixt) 15s
• Pulse utilisation over the last 15 seconds (only for
loads >160 %).
C00064/3
Device utilisation (Ixt) 3 min
• Permanent utilisation over the last 3 minutes.
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100