C00605 | resp. to feedback, C00606 | resp. to motor overload (i·xt), C00607 | resp. to max freq. feedb. dig12/67 – Lenze 8400 HighLine User Manual
Page 925: C00608 | resp. to maximum torque, C00607, C00606, C00608, Set in, Onse set in, 15 parameter reference
![background image](/manuals/566310/925/background.png)
Lenze · 8400 HighLine · Referenzhandbuch · DMS 10.0 EN · 06/2014 · TD05/TD14
925
15
Parameter reference
15.2
Parameter list | C00605
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00605
C00606
C00607
C00608
Parameter | Name:
C00605 | Resp. to feedback
Data type: UNSIGNED_8
Index: 23970
d
= 5DA2
h
From version 15.00.00
Selection list
0 No Reaction
1 Fault
2 Trouble
3 TroubleQuickStop
4 WarningLocked
5 Warning
6 Information
Subcodes
Lenze setting
Info
C00605/1
1: Fault
Resp. to open circuit HTL 4-fold
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00606 | Resp. to motor overload (I²xt)
Data type: UNSIGNED_8
Index: 23969
d
= 5DA1
h
Response when the motor load displayed in
reaches the value "100.00 %".
Motor overload monitoring (I2xt)
Selection list
(Lenze setting printed in bold)
0 No Reaction
1 Fault
5 Warning
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00607 | Resp. to max freq. feedb. DIG12/67
Data type: UNSIGNED_8
Index: 23968
d
= 5DA0
h
Response when the maximum input frequency has been reached via the digital inputs.
Selection list
(Lenze setting printed in bold)
0 No Reaction
1 Fault
5 Warning
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00608 | Resp. to maximum torque
Data type: UNSIGNED_8
Index: 23967
d
= 5D9F
h
Response if the maximum torque (
) is reached.
Selection list
(Lenze setting printed in bold)
0 No Reaction
1 Fault
5 Warning
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1