2 notes on motor control, Notes on motor control, 3commissioning – Lenze 8400 HighLine User Manual
Page 52
3
Commissioning
3.2
Notes on motor control
52
Lenze · 8400 HighLine · Referenzhandbuch · DMS 10.0 EN · 06/2014 · TD05/TD14
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
3.2
Notes on motor control
In the Lenze setting, the V/f characteristic control (VFCplus) as motor control is set in
with
a linear characteristic.
• V/f characteristic control (VFCplus) is a motor control mode for classic frequency inverter
applications on the basis of a simple and robust control procedure for the operation of machines
with a linear or quadratic load torque characteristic (e.g. fans).
• The presettings of the parameters ensure that the controller is immediately ready for operation
and the motor works adequately without further parameterisation if a controller and a 50 Hz
asynchronous machine with matching performances are assigned to each other.
Recommendations for the following application cases:
• If the controller and motor differ greatly in terms of performance:
Set the Imax limit (in motor mode) in
• If a high starting torque is required:
When the motor is idling, set a value for Vmin boost in
which ensures that the rated
motor current flows at a field frequency of f = 3 Hz (display in
• For noise optimisation:
In
, set a switching frequency of "16 kHz var./drive-opt.".
• If a high torque must be provided at small speeds without feedback:
Select "Sensorless vector control (SLVC) as motor control mode in
Related topics:
Note!
Check the nameplate data against the motor data set in the controller. Further
information is provided in the chapter "