I-1201, 11 system bus "can on board – Lenze 8400 HighLine User Manual
Page 750
11
System bus "CAN on board"
11.11
Implemented CANopen objects | I-1201
750
Lenze · 8400 HighLine · Referenzhandbuch · DMS 10.0 EN · 06/2014 · TD05/TD14
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
I-1201
Identifiers for SDO server channel 2.
• The SDO server parameter is only valid, if bit 31 is set to "0" for both transmission directions
(subindex 1 and 2).
• In the Lenze setting, the SDO server channels 2 are deactivated (bit 31 = "1").
• The identifier can only be changed if the SDO is invalid (bit 31 = "1").
[11-6] Data telegram assignment
How to change the identifier:
1. Deactivate identifier (set bit 31 to "1").
2. Change identifier.
3. Activate identifier (set bit 31 to "0").
Index:
I-1201
Name:
SDO2 server parameter
Subindex
Default setting
Setting range (min. value | unit | max. value)
Access
Data type
0: Highest subindex supported
3
- (read access only)
ro
U8
1: COB-ID client -> server (rx)
0x80000000
0
4294967295 rw
U32
2: COB-ID server -> client (tx)
0x80000000
0
4294967295 rw
U32
Subindex
Meaning
1
Specification of receive identifier
2
Specification of send identifier
8th byte
7th byte
6th byte
5th byte
Data 4
Data 3
Data 2
Data 1
Bit 31
Bit 30
Bit 29 ... bit 11
Bit 10 ... bit 0
0/1
0
Extended identifier*
11-bit identifier
* The extended identifier is not supported. Bit 11 ... bit 29 must be set to "0".
Bit
Setting
Bit 31
0 SDO is valid.
1 SDO is invalid.