C00593 | resp. to canx_in monitoring, C00594 | resp. to control word error, C00594/1 – Lenze 8400 HighLine User Manual
Page 921: C00594/2, C00593/1, C00593/2, C00593/3, C00593/4, 15 parameter reference

Lenze · 8400 HighLine · Referenzhandbuch · DMS 10.0 EN · 06/2014 · TD05/TD14
921
15
Parameter reference
15.2
Parameter list | C00593
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00593
C00594
Parameter | Name:
C00593 | Resp. to CANx_IN monitoring
Data type: UNSIGNED_8
Index: 23982
d
= 5DAE
h
Configuration of monitoring of the CAN interface (group 2)
Selection list
0 No Reaction
1 Fault
2 Trouble
3 TroubleQuickStop
4 WarningLocked
5 Warning
6 Information
Subcodes
Lenze setting
Info
C00593/1
0: No Reaction
Response if the monitoring time set in
for the
reception of the PDO CAN1_IN is exceeded.
C00593/2
0: No Reaction
Response if the monitoring time set in
for the
reception of the PDO CAN2_IN is exceeded.
C00593/3
0: No Reaction
Response if the monitoring time set in
for the
reception of the PDO CAN3_IN is exceeded.
C00593/4
0: No Reaction
Response if the monitoring time set in
for the
reception of the PDO CAN4_IN is exceeded.
•
From version 15.00.00
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00594 | Resp. to control word error
Data type: UNSIGNED_8
Index: 23981
d
= 5DAD
h
Configuration of device control monitoring
Selection list
0 No Reaction
1 Fault
2 Trouble
3 TroubleQuickStop
5 Warning
Subcodes
Lenze setting
Info
C00594/1
1: Fault
Response if error bit 14 in the CAN control word is set.
C00594/2
1: Fault
Response if error bit 14 in the MCI control word is set.
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1