C00761 | la_switchpos: digital connection list, C00761/4, C00761/x – Lenze 8400 HighLine User Manual
Page 965: 15 parameter reference
Lenze · 8400 HighLine · Referenzhandbuch · DMS 10.0 EN · 06/2014 · TD05/TD14
965
15
Parameter reference
15.2
Parameter list | C00761
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00761
C00760/22
0: Not connected
: wFreeIn1
Input for user signal 1
C00760/23
0: Not connected
: wFreeIn2
Input for user signal 2
C00760/24
0: Not connected
: wFreeIn3
Input for user signal 3
C00760/25
0: Not connected
: wFreeIn4
Input for user signal 4
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00760 | LA_SwitchPos: Analog connection list
Data type: UNSIGNED_16
Index: 23815
d
= 5D07
h
Parameter | Name:
C00761 | LA_SwitchPos: Digital connection list
Data type: UNSIGNED_16
Index: 23814
d
= 5D06
h
Connection parameters for "Switch-off positioning" application: Binary inputs
• Selection of the binary output signals to be connected to the binary input signals
• The selection list contains all binary output signals which can be assigned to the binary inputs mapped by the
subcodes.
Selection list
See
selection list - digital signals
Subcodes
Lenze setting
Info
C00761/1
0: Not connected
: bCInh
Control input for setting controller inhibit
C00761/2
0: Not connected
: bFailReset
Control input for error acknowledgement
C00761/3
0: Not connected
: bSetQuickstop
Control input for quick stop request
C00761/4
0: Not connected
: bSetDCBrake
Control input for DC-injection braking request
C00761/5
0: Not connected
: bRFG_Stop
Control input for stopping the speed ramp function
generator
C00761/6
0: Not connected
: bSetSpeedCcw
Control input for change of direction of rotation
C00761/7
0: Not connected
: bRLQCw
Control input for activation of CW rotation (fail-safe)
C00761/8
0: Not connected
: bRLQCcw
Control input for activation of CCW rotation (fail-safe)
C00761/9
0: Not connected
: bJogCtrlInputSel1
Selection input 1 for binary coded selection of the
switch-off position 1 ... 3
C00761/10
0: Not connected
: bJogCtrlInputSel2
Selection input 2 for binary coded selection of the
switch-off position 1 ... 3
C00761/11
0: Not connected
: bJogCtrlRfgIn
Control input for setpoint generator ramp-down
C00761/12
0: Not connected
: bJogCtrlJog1
Selection input 1 for overriding fixed setpoints (JOG
setpoints) for the main setpoint
C00761/13
0: Not connected
: bJogCtrlJog2
Selection input 2 for overriding fixed setpoints (JOG
setpoints) for the main setpoint