11.8.2
Identifiers of the process data objects
For the process data objects PDO1 ... PDO4, three identifier assignment procedures are available in
:
• Identifier (COB-ID) = node address (C00350) + CANBaseID (Lenze setting)
• Identifier (COB-ID) = node address (C00350) + LenzeBaseID
• Identifier (COB-ID) = C0354/x
Lenze setting: Basic identifiers according to the "Predefined Connection Set" of DS301 V4.02
In the Lenze setting, the identifiers for the process data objects PDO1 ... PDO4 consist of the node
address set in
and a basic identifier (CANBaseID) which corresponds to the "Predefined
Connection Set" of DS301 V4.02:
Tip!
The active identifiers (COB-ID) are displayed in
OPTIONAL: Use the basic identifier according to Lenze definition (LenzeBaseID)
If the basic identifiers shall be used instead according to the Lenze definition, go to
and
select "0: COBID = C0350 + LenzeBaseID" for the coresponding PDO.
The basic Lenze identifiers which differ from the "Predefined Connection Set" are highlighted in
colour in the following table:
Object
Basis identifier (CANBaseID)
PDO1
TPDO1
COB-ID = node address (
) +
384
0x180
RPDO1
512
0x200
PDO2
TPDO2
640
0x280
RPDO2
768
0x300
PDO3
TPDO3
896
0x380
RPDO3
1024
0x400
PDO4
TPDO4
1152
0x480
RPDO4
1280
0x500
Object
Basic identifier (LenzeBaseID)
PDO1
TPDO1
COB-ID = node address (
) +
384
0x180
RPDO1
512
0x200
PDO2
TPDO2
640
0x280
RPDO2
641
0x281
PDO3
TPDO3
768
0x300
RPDO3
769
0x301
PDO4
TPDO4
896
0x380
RPDO4
897
0x381