Internal interfaces to the application
• Relevant inputs at the
system block:
• Relevant outputs at the
system block:
Identifier
DIS code | data type
Information/possible settings
Counting input DI1
bCountIn1_ResetCompare
BOOL
Reset status signal "Comparison value reached"
FALSETRUE The output bCountIn1_Compare is reset to FALSE.
bCountIn1_LoadStartValue
BOOL
Load starting value into counter
FALSETRUE The starting value set in
is accepted as the current count
value.
Counting input DI6
bCountIn6_ResetCompare
BOOL
Reset status signal "Comparison value reached"
FALSETRUE The output bCountIn6_Compare is reset to FALSE.
bCountIn6_LoadStartValue
BOOL
Load starting value into counter
FALSETRUE The starting value set in
is accepted as the current count
value.
Identifier
DIS code | data type
Value/meaning
Counting input DI1
bCountIn1_Compare
BOOL
Status signal "Comparison value reached"
FALSE Current count value < comparison value (
)
TRUE Current count value ≥ comparison value (
)
wCountIn1_HW
wCountIn1_LW
| WORD
Current count value
• Output as High and Low word (without sign)
• Possible counting range: 0 ... 2
31
- 1
Counting input DI6
bCountIn6_Compare
BOOL
Status signal "Comparison value reached"
FALSE Current count value < comparison value (
)
TRUE Current count value ≥ comparison value (
)
wCountIn6_HW
wCountIn6_LW
| WORD
Current count value
• Output as High and Low word (without sign)
• Possible counting range: 0 ... 2
31
- 1