C00079 | sc: settings, C00080 | override point of field weakening, C00081 | rated motor power – Lenze 8400 HighLine User Manual
Page 819: C00081, Rate, C00080, Controller feedforward control, C00079/1, C00079/4, Tive
Lenze · 8400 HighLine · Referenzhandbuch · DMS 10.0 EN · 06/2014 · TD05/TD14
819
15
Parameter reference
15.2
Parameter list | C00079
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00079
C00080
C00081
Parameter | Name:
C00079 | SC: Settings
Data type: UNSIGNED_8
Index: 24496
d
= 5FB0
h
Configuration of different options for servo control (
) and sensorless control for synchronous motors (
)
Selection list
0 Off
1 On
Subcodes
Lenze setting
Info
C00079/1
0: Off
: Current controller - feedforward control
• Please observe the notes regarding this function in
the chapter "
Feedforward control of the current
"!
C00079/2
1: On
: Adapt. VP in the field weakening range
• Speed-dependent adaptive field weakening
controller.
C00079/3
0: Off
: n-ctrl anti-wind-up
• "Anti-wind-up" effect of the speed controller in case
of an output voltage limitation in the field weakening
range.
C00079/4
1: On
Field weakening for synchronous motors
•
From version 11.00.00
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00080 | Override point of field weakening
Data type: INTEGER_16
Index: 24495
d
= 5FAF
h
Offset of the override point of field weakening
• In the V/f characteristic control mode (
), the stall protection function or the max. permissible current in
the field weakening range can be adapted.
Setting range
(min. value | unit | max. value)
Lenze setting
-500
Hz
500 0 Hz
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00081 | Rated motor power
Data type: UNSIGNED_16
Index: 24494
d
= 5FAE
h
This value can be obtained from the motor nameplate. After the motor to be used has been selected from the motor
catalogue, the suitable value can be entered automatically.
Note:
It is mandatory to give the rated motor power for the sensorless vector control (
) and the servo control (
Setting range
(min. value | unit | max. value)
Lenze setting
0.00
kW
500.00 11.00 kW
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100