C00693 | l_compare 4-5: function, C00694 | l_compare 4-5: hysteresis, C00695 | l_compare 4-5: window – Lenze 8400 HighLine User Manual
Page 949: C00696 | l_offsetgainp_1: offset, C00696, Can be set in, T in, 15 parameter reference

Lenze · 8400 HighLine · Referenzhandbuch · DMS 10.0 EN · 06/2014 · TD05/TD14
949
15
Parameter reference
15.2
Parameter list | C00693
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00693
C00694
C00695
C00696
Parameter | Name:
C00693 | L_Compare 4-5: Function
Data type: UNSIGNED_8
Index: 23882
d
= 5D4A
h
Comparison operation
• If the statement of the selected comparison operation is true, the binary bOut output will be set to TRUE.
Selection list
1 In1 = In2
2 In1 > In2
3 In1 < In2
4 |In1| = |In2|
5 |In1| > |In2|
6 |In1| < |In2|
Subcodes
Lenze setting
Info
C00693/1
1: In1 = In2
: Function
C00693/2
1: In1 = In2
: Function
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00694 | L_Compare 4-5: Hysteresis
Data type: INTEGER_16
Index: 23881
d
= 5D49
h
Hysteresis for the comparison operation selected in
Setting range
(min. value | unit | max. value)
0.00
%
100.00
Subcodes
Lenze setting
Info
C00694/1
0.00 %
C00694/2
0.00 %
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100
Parameter | Name:
C00695 | L_Compare 4-5: Window
Data type: INTEGER_16
Index: 23880
d
= 5D48
h
Window for the comparison operation selected in
Setting range
(min. value | unit | max. value)
0.00
%
100.00
Subcodes
Lenze setting
Info
C00695/1
0.00 %
: Window
C00695/2
0.00 %
: Window
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100
Parameter | Name:
C00696 | L_OffsetGainP_1: Offset
Data type: INTEGER_16
Index: 23879
d
= 5D47
h
FB: Offset (additive to the input signal)
Setting range
(min. value | unit | max. value)
Lenze setting
-199.99
%
199.99 0.00 %
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100