I-1403/1, I-1403, 11 system bus "can on board – Lenze 8400 HighLine User Manual
Page 755
![background image](/manuals/566310/755/background.png)
Lenze · 8400 HighLine · Referenzhandbuch · DMS 10.0 EN · 06/2014 · TD05/TD14
755
11
System bus "CAN on board"
11.11
Implemented CANopen objects | I-1403
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
I-1403
From version 15.00.00
Communication parameter for receiving process data via RPDO4
• For data telegram assignment and description of subindices 1 and 2, see object
.
How to change the identifier:
1. Deactivate identifier (set bit 31 to "1").
2. Change identifier.
3. Activate identifier (set bit 31 to "0").
Index:
I-1403
Name:
RPDO4 communication parameter
Subindex
Default setting
Setting range (min. value | unit | max. value)
Access
Data type
0: Highest subindex supported
5
- (read access only)
ro
U8
1: COB-ID used by RPDO
0x500 + node ID
0
4294967295 rw
U32
2: Transmission type
254
0
255 rw
U8
3: Inhibit time
-
- (not used for RPDOs)
rw
U16
4: Compatibility entry
-
- (reserved, read or write access leads to error message
0x06090011)
rw
U8
5: Event timer
-
- (not used for RPDOs)
rw
U16
Subindex
Meaning
Code
0
"5" is permanently set.
• Max. 5 subindices are supported.
-
1
Identifier RPDO4
• According to the "Predefined Connection Set", the
basic setting is: Identifier = 0x500 + node ID
2
RPDO transmission type according to DS301 V4.02