Error messages of the operating system
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
oC10: Maximum current reached [xx.0123.00030]
oC17: Clamp sets pulse inhibit [xx.0123.00031]
oS1: Maximum speed limit reached [xx.0123.00032]
oS2: Max. motor speed [xx.0123.00033]
Id1: Motor data identification error [xx.0123.00057]
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
The device displays that the maximum current has been
reached.
• Check and, if required, correct dimensioning of the
load with regard to the installed device power.
• Check the maximum current settings in
(Imax in motor mode) and
(Imax in generator
mode).
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
Due to a short overcurrent, the inverter was switched off
for a short time (clamp disconnection).
• Check and, if required, correct dimensioning of the
load with regard to the installed device power.
• Reduce the dynamics of the setpoint change or speed
control.
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
The device has recognised that the maximum speed has
been reached.
• Limit setpoint selection to maximum values.
• Adjust set speed limitation (
) and frequency
limitation (
Response (Lenze setting printed in bold)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
The device has recognised that the maximally
permissible motor speed has been reached.
• Limit setpoint selection to the maximally permissible
motor speed.
• If required, adapt set maximum motor speed
(
).
Response (Lenze setting printed in bold)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
During the identification of motor parameters, an error
has occurred.
Possible causes:
• Interrupted motor cable.
• Switched-off power section during the identification.
• Implausible start parameter settings.
• Check the motor connections and the corresponding
plug connector on the device and, if necessary, the
motor terminal box.
• Correct start parameters for the motor parameter
identification (motor nameplate data).
• Stable power supply of the device.