Parameter list | C00029
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00029
C00033
C00034
Parameter | Name:
C00029 | AINx: Input current
Data type: INTEGER_16
Index: 24546
d
= 5FE2
h
Display of the input current at the analog inputs
• When the corresponding analog input is configured for current measurement (
= 1 or 2).
is set = 2 (4 ... 20 mA), 0 ... 16 mA is displayed.
Display range
(min. value | unit | max. value)
0.00
mA
20.00
Subcodes
Info
C00029/1
AIN1: Input current
C00029/2
AIN2: Input current
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100
Parameter | Name:
C00033 | AINx: Output value
Data type: INTEGER_16
Index: 24542
d
= 5FDE
h
Display of the output value in percent of the analog input amplifier
• 100 % ≡ 16384 ≡ +10 V / +20 mA
Display range
(min. value | unit | max. value)
-199.99
%
199.99
Subcodes
Info
C00033/1
AIN1: Output value
C00033/2
AIN2: Output value
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100
Parameter | Name:
C00034 | AINx: Configuration
Data type: UNSIGNED_8
Index: 24541
d
= 5FDD
h
Configuration of the analog inputs for current or voltage measurement
Selection list
Info
0 -10V..+10V
Input signal is the voltage signal -10 V ... +10 V
• -10 V ... +10 V ≡ -100 % ... +100 %
1 0mA..20mA
Input signal is the current signal 0 mA ... 20 mA
• 0 mA ... 20 mA ≡ 0 % ... +100 %
2 4mA..20mA
Input signal is the current signal 4 mA ... 20 mA
• 4 mA ... 20 mA ≡ 0 % ... +100 %
• The current loop is monitored for open circuit
(I < 4 mA) by the device.
Subcodes
Lenze setting
Info
C00034/1
0: -10V..+10V
AIN1: Config.
C00034/2
0: -10V..+10V
AIN2: Config.
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1