C00600 | resp. to dc bus voltage, C00601 | del. resp. to fault: dc bus overvoltage, C00602 | resp. to earth fault – Lenze 8400 HighLine User Manual
Page 924: C00604 | resp. to device overload (ixt), Epending on, C00600/1, C00604, C00601, C00602, To "0

15
Parameter reference
15.2
Parameter list | C00600
924
Lenze · 8400 HighLine · Referenzhandbuch · DMS 10.0 EN · 06/2014 · TD05/TD14
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00600
C00601
C00602
C00604
Parameter | Name:
C00600 | Resp. to DC bus voltage
Data type: UNSIGNED_8
Index: 23975
d
= 5DA7
h
Configuration of monitoring of the motor control (group 3)
Selection list
1 Fault
2 Trouble
Subcodes
Lenze setting
Info
C00600/1
2: Trouble
Response to DC bus undervoltage
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00601 | Del. resp. to fault: DC bus overvoltage
Data type: UNSIGNED_16
Index: 23974
d
= 5DA6
h
Error response delay times
Setting range
(min. value | unit | max. value)
0.000
s
65.000
Subcodes
Lenze setting
Info
C00601/1
2.000 s
Delay time for triggering the "DC-bus overvoltage" error
• If a DC-bus overvoltage occurs, an error will not be
triggered until the set delay time has elapsed.
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1000
Parameter | Name:
C00602 | Resp. to earth fault
Data type: UNSIGNED_8
Index: 23973
d
= 5DA5
h
Response to earth fault in the motor phase(s)
Selection list
(Lenze setting printed in bold)
0 No Reaction
1 Fault
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00604 | Resp. to device overload (Ixt)
Data type: UNSIGNED_8
Index: 23971
d
= 5DA3
h
Response if the adjustable device utilisation threshold (
• The current device utilisation is displayed in
Selection list
(Lenze setting printed in bold)
0 No Reaction
1 Fault
5 Warning
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1