INTELLIGENT ACTUATOR
Chapter 4 Commands
2.
Explanation
of
Commands
z BTPN (Output ON pulse)
Command, declaration
Extension condition
(LD, A, O, AB, OB)
Input condition
(I/O, flag)
Command, 
declaration 
Operand 1
Operand 2
Output
(Output, flag)
Optional Optional
BTPN
Output port,
flag
Timer setting
CP
[Function]
Turn ON the specified output port or flag for the specified time. 
When this command is executed, the output port or flag specified in operand 1 will be turned 
ON and then the program will proceed to the next step. The output port or flag will be turned 
OFF automatically upon elapse of the timer setting specified in operand 2. 
The timer is set in a range from 0.01 to 99.00 seconds (including up to two decimal places).
(Note 1)
If this command is executed with respect to an output port or flag already ON, the output 
port or flag will be turned OFF upon elapse of the timer setting. 
(Note 2)
If the program ends after the command has been executed but before the timer is up, the 
output port or flag will not be turned OFF. 
(Note 3)
This command will not be cancelled by a TIMC command.
(Note 4)
A maximum of 16 timers, including BTPN and BTPF, can be operated simultaneously in a 
single program. (There is no limitation as to how many times these timers can be used in a 
single program.) 
[Example]
BTPN
316
1
Turn ON output port 316 for 1 second.
BTPN
600
10
Turn ON flag 600 for 10 seconds.
Timer setting (seconds)
The output port or flag turns ON here, after 
which the program will proceed to the next step.
ON
OFF