Compiler Errors and Warnings

DMS 3.2 EN 02/2011 TD29

595

3601

" is a reserved variable name"

The given variable is declared in the project, although it is reserved for the
codegenerator. Rename the variable.

3610

" '' not supported"

The given feature is not supported by the current version of the programming system.

3611

"The given compile directory '' is invalid"

There is an invalid directory given in the ‚Project’ ‚Options’ ‚Directories’ for the
Compile files.

3612

"Maximum number of POUs () exceeded! Compile is aborted."

Too many POUs and data types are used in the project. Modify the maximum number
of POUs in the Target Settings / Memory Layout.

3613

"Build canceled"

The compile process was cancelled by the user.

3614

"Project must contain a POU named '' (main routine) or a taskconfiguration"

Create an init POU of type Program (e.g. PLC_PRG) or set up a task configuration.

3615

" (main routine) must be of type program"

A init POU (e.g. PLC_PRG) is used in the project which is not of type Program.