Page 578
13 - 4
MELSEC-Q
13 COMMON FUNCTIONS
[4] Parameter initialization method
(1) Parameter initialization is carried out using the dedicated instruction "PINIT".
(Refer to Chapter 14 "Dedicated instructions" for details.)
(2) Parameter initialization can also be carried out by the writing of the data
shown in the table below to the buffer memory using the TO
command/intelligent function device.
The initialization of the parameter is executed at the time point the data is
written to the QD75 buffer memory.
Buffer memory address
Setting item
Setting
value
Setting details
Axis
1
Axis
2
Axis
3
Axis
4
Cd.2
Parameter
initialization request
1
Set "1" (parameter initialization request).
1901
Refer to Section 5.7 "List of control data" for details on the setting details.
When the initialization is complete, "0" will be set in " Cd.2 Parameter
initialization request" by the QD75 automatically.