12 CONTROL SUB FUNCTIONS

[3] Deceleration start flag function setting method

To use the "deceleration start flag function", set "1" to the following control data

using a sequence program.

The set data is made valid on the rising edge (OFF to ON) of the PLC READY

signal [Y0].

Setting item

Setting

value

Setting details

Buffer memory address

Cd

.41

Deceleration start
flag valid

Set whether the deceleration start flag function
is made valid or invalid.

0: Deceleration start flag invalid

1: Deceleration start flag valid

1905

Refer to Section 5.7 "List of control data" for details on the setting details.

[4] Checking of deceleration start flag

The "deceleration start flag" is stored into the following buffer memory addresses.

Buffer memory address

Monitor item

Monitor

value

Storage details

Axis

1

Axis

2

Axis

3

Axis

4

Md

.48

Deceleration start
flag

0: Status other than below

1: Status from deceleration start to next

operation start or manual pulse generator
operation enable

899

999 1099 1199

Refer to Section 5.6 "List of monitor data" for information on the storage details.