Melsec-q, 9 major positioning control – MITSUBISHI ELECTRIC Mitsubishi Programmable Logic Controller QD75D User Manual
Page 376

9 - 76
MELSEC-Q
9 MAJOR POSITIONING CONTROL
Positioning data setting examples
The following table shows the setting examples when "3-axis speed control
(forward run: speed 3)" is set in the positioning data No. 1 of axis 1 (reference
axis).
Axis
Setting item
Axis 1
(reference
axis) setting
example
Axis 2
(interpolation
axis) setting
example
Axis 3
(interpolation
axis) setting
example
Setting details
Da.1 Operation pattern
Positioning
complete
–
–
Setting other than "Positioning complete" is
not possible in speed control.
Da.2 Control system
Forward run
speed 3
–
–
Set 3-axis speed control.
Da.3
Acceleration time
No.
1
–
–
Designate the value set in " Pr.25
Acceleration time 1" as the acceleration time
at start.
Da.4
Deceleration time
No.
0
–
–
Designate the value set in " Pr.10
Deceleration time 0" as the deceleration time
at deceleration.
Da.5
Axis to be
interpolated
–
–
–
Setting not required (setting value will be
ignored).
When axis 1 is used as a reference axis, the
interpolation axes are axes 2 and 3.
Da.6
Positioning address/
movement amount
–
–
–
Setting not required (setting value will be
ignored).
Da.7 Arc address
–
–
–
Setting not required (setting value will be
ignored).
Da.8 Command speed
6000.00
mm/min
3000.00
mm/min
2000.00
mm/min
Set the speed to be commanded.
Da.9 Dwell time
–
–
–
Setting not required (setting value will be
ignored).
A
x
is 1 Positioning data N
o
. 1
Da.10 M code
10
–
–
Set this when other sub operation commands
are issued in combination with the No. 1
positioning data. (" Pr.18 M code ON signal
output timing" setting only possible in the
WITH mode.)
Refer to Section 5.3 "List of positioning data" for information on the setting details.