4 creating start programs for jog operation, Melsec-q – MITSUBISHI ELECTRIC Mitsubishi Programmable Logic Controller QD75D User Manual
Page 450
11 - 10
MELSEC-Q
11 MANUAL CONTROL
11.2.4 Creating start programs for JOG operation
A sequence program must be created to execute a JOG operation. Consider the
"required control data setting", "start conditions" and "start time chart" when creating
the program.
The following shows an example when a JOG operation is started for axis 1.
("
Cd.17
JOG speed" is set to "100.00mm/min" in the example shown.)
Required control data setting
The control data shown below must be set to execute a JOG operation. The
setting is carried out with the sequence program.
Buffer memory address
Setting item
Setting
value
Setting details
Axis
1
Axis
2
Axis
3
Axis
4
Cd.16
Inching movement
amount
0
Set “0”.
1517 1617 1717 1817
Cd.17
JOG speed
10000
Set a value equal to or above the "
Pr.7
Bias
speed at start" and equal to or below the
" Pr.31 JOG speed limit value".
1518
1519
1618
1619
1718
1719
1818
1819
Refer to Section 5.7 "List of control data" for details on the setting details.
Start conditions
The following conditions must be fulfilled when starting. The required conditions
must also be assembled in the sequence program, and the sequence program
must be configured so the operation will not start if the conditions are not fulfilled.
Device
Signal name
Signal state
Axis
1
Axis
2
Axis
3
Axis
4
PLC READY signal
ON PLC CPU preparation completed
Y0
QD75 READY signal
ON QD75 preparation completed
X0
Synchronization flag
ON
QD75 buffer memory
The access is possible.
X1
Axis stop signal
OFF Axis stop signal is OFF
Y4
Y5
Y6
Y7
Start complete signal
OFF Start complete signal is OFF
X10 X11 X12 X13
BUSY signal
OFF QD75 is not operating
XC
XD
XE
XF
Error detection signal
OFF There is no error
X8
X9
XA
XB
Interface
signal
M code ON signal
OFF M code ON signal is OFF
X4
X5
X6
X7
Drive unit READY signal
ON Drive unit preparation completed
–
Stop signal
OFF Stop signal is OFF
–
Upper limit (FLS)
ON Within limit range
–
External
signal
Lower limit (RLS)
ON Within limit range
–
If the PLC CPU is set to the asynchronous mode in the synchronization setting, this must be
inserted in the program for interlocking. If it is set to the synchronous mode, it must not be
inserted in the program for interlocking because it is turned ON when the PLC CPU executes
calculation.