MELSEC-Q

10 HIGH-LEVEL POSITIONING CONTROL

10.3.8 Restrictions when using the NEXT start

The "NEXT start" is a instruction indicating the end of the repetitions when executing

Section 10.3.6 "Repeated start (FOR loop)" and Section 10.3.7 "Repeated start (FOR

condition)".

The following shows the restrictions when setting "6: NEXT start" in the " block start

data".

(1)

The processing when "6: NEXT start" is set before execution of "4: FOR loop" or

"5: FOR condition" is the same as that for a "0: block start".

(2)

Repeated processing will not be carried out if there is no "6: NEXT start"

instruction after the "4: FOR loop" or "5: FOR condition" instruction. (Note that an

"error" will not occur.)

(3)

Nesting is not possible between "4: FOR loop" and "6: NEXT start", or between

"5: FOR condition" and "6: NEXT start". A warning "FOR to NEXT nest

construction (warning code: 506)" will occur if nesting is attempted.

[Operating examples without nesting structure]

[Operating examples with nesting structure]

Start block data

Da.12 Special start

command

Start block data

Da.12 Special start

command

1st point

Normal start

1st point

Normal start

2nd point

FOR

2nd point

FOR

3rd point

Normal start

3rd point

Normal start

4th point

NEXT

4th point

FOR

5th point

Normal start

5th point

Normal start

6th point

Normal start

6th point

Normal start

7th point

FOR

7th point

NEXT

8th point

Normal start

8th point

Normal start

9th point

NEXT

9th point

NEXT

A warning will occur when starting the 4th
point "FOR".
The JUMP destination of the 7th point "NEXT"
is the 4th point. The 9th point "NEXT" is
processed as normal start.