MELSEC-Q
10 HIGH-LEVEL POSITIONING CONTROL
10.3.8 Restrictions when using the NEXT start
The "NEXT start" is a instruction indicating the end of the repetitions when executing
Section 10.3.6 "Repeated start (FOR loop)" and Section 10.3.7 "Repeated start (FOR
condition)".
The following shows the restrictions when setting "6: NEXT start" in the " block start
data".
(1)
The processing when "6: NEXT start" is set before execution of "4: FOR loop" or
"5: FOR condition" is the same as that for a "0: block start".
(2)
Repeated processing will not be carried out if there is no "6: NEXT start"
instruction after the "4: FOR loop" or "5: FOR condition" instruction. (Note that an
"error" will not occur.)
(3)
Nesting is not possible between "4: FOR loop" and "6: NEXT start", or between
"5: FOR condition" and "6: NEXT start". A warning "FOR to NEXT nest
construction (warning code: 506)" will occur if nesting is attempted.
[Operating examples without nesting structure]
[Operating examples with nesting structure]
Start block data
Da.12 Special start
command
Start block data
Da.12 Special start
command
1st point
Normal start
1st point
Normal start
2nd point
FOR
2nd point
FOR
3rd point
Normal start
3rd point
Normal start
4th point
NEXT
4th point
FOR
5th point
Normal start
5th point
Normal start
6th point
Normal start
6th point
Normal start
7th point
FOR
7th point
NEXT
8th point
Normal start
8th point
Normal start
9th point
NEXT
9th point
NEXT
•
•
•
•
A warning will occur when starting the 4th
point "FOR".
The JUMP destination of the 7th point "NEXT"
is the 4th point. The 9th point "NEXT" is
processed as normal start.